Diesel generator maintenance checklist, daily to annual.

What to check on a DG set, how often, and what to write down. Intervals and quantities always come from your engine manufacturer's manual.

  • Daily
  • Weekly
  • Monthly
  • Service interval
  • Annual

Checklist 1 of 5

Daily (or before every start)

A walk-round by the operator. Takes a few minutes and catches most problems early.

  • Engine oil level on the dipstick — between the marks, not above the upper mark.
  • Coolant level in the expansion tank (check only when the engine is cold).
  • Fuel level in the day tank, and no water or sludge at the drain point.
  • Look under and around the set for oil, fuel or coolant leaks.
  • Battery charger on and showing charge; no alarms on the controller.
  • Controller in AUTO mode (for AMF sets) and the emergency stop released.
  • Air intake and radiator not blocked by cloth, cartons or dust.

Checklist 2 of 5

Weekly

Run the set and look at it working, not just standing still.

  • Run the generator on load where the site allows it — a no-load run does little for a diesel engine (see load test).
  • While it runs: oil pressure, coolant temperature, voltage and frequency steady and in the normal band on the controller.
  • Exhaust colour: no persistent black, blue or white smoke once warm.
  • Unusual noise or vibration from the engine, alternator or mountings.
  • Air filter restriction indicator, where fitted.
  • Battery terminals clean and tight; electrolyte level on flooded batteries.
  • Log hours run, fuel added and any alarm seen.

Checklist 3 of 5

Monthly

Wear items and anything that loosens with vibration.

  • Fan and alternator belts for cracks, glazing and tension.
  • Radiator fins and hoses — clean the core, look for soft or swollen hoses and weeping clamps.
  • Fuel water separator: drain water; check fuel lines and joints.
  • Exhaust system for leaks, loose clamps and condition of the flexible joint.
  • Earthing connections and cable terminations at the alternator and panel.
  • Battery voltage at rest and while cranking.
  • Canopy doors, seals and the DG room ventilation path.

Checklist 4 of 5

Every service interval (typically half-yearly or by run hours)

The scheduled service. Intervals come from the engine manufacturer's manual — whichever of hours or months comes first.

  • Change engine oil and oil filter.
  • Replace fuel filters; replace or clean the air filter element as specified.
  • Check coolant strength and condition; top up with the specified coolant, not plain water.
  • Check valve clearances and injector condition where the manual calls for it.
  • Tighten electrical connections in the control panel and AMF panel.
  • Test safety shutdowns — low oil pressure, high coolant temperature, overspeed — as the controller allows.
  • Run a load test and record the readings (see below).

Checklist 5 of 5

Annually

A deeper inspection, usually done by the service engineer.

  • Alternator insulation resistance test and cleaning of the windings and vents.
  • Coolant flush and replacement if due per the manual.
  • Inspect the turbocharger, intercooler and engine mountings.
  • Calibrate or check gauges, sensors and the controller's protection settings.
  • Check the AMF / changeover operation end to end: mains fail, start, transfer, restore, cool-down.
  • Review the year's log: run hours, fuel used, alarms, recurring faults — and plan any overhaul.
  • Emission-control compliance where applicable (CPCB norms, RECD condition).

Log book

What to record every time.

A checklist without a log only tells you the set was looked at. The log is what shows a trend — rising oil use, falling battery voltage, more fuel per hour.

  • Date, hour-meter reading and who did the check
  • Fuel added and fuel level before and after
  • Oil and coolant added
  • Readings on load: kW, power factor, voltage, frequency, oil pressure, coolant temperature
  • Alarms or shutdowns and what caused them
  • Parts replaced and the next service due (hours or date)

Need an engineer to do the scheduled work? Our generator AMC covers it, and the generator load test guide explains the on-load readings.

Monitor it continuously

Let the generator keep its own log.

A Titan energy meter records DG run hours, units generated, load and power factor on its own, and can read oil pressure, coolant temperature, fuel level and alarms from the genset controller — so the log book fills itself between visits.

Frequently asked questions

How often should a diesel generator be serviced?

Follow the engine manufacturer's manual — service intervals are set in run hours and in months, whichever comes first. Standby sets that run very little still need time-based service because oil, coolant, fuel and batteries age without running.

What is checked during DG set maintenance?

Fuel, lubrication, cooling, air intake, exhaust, battery and starting system, the alternator and the control/AMF panel. The checklist above splits these into daily, weekly, monthly, service-interval and annual tasks.

Is running the generator without load enough?

No. A diesel engine run for long periods on no or light load does not reach proper operating temperature, which can lead to unburnt fuel and carbon build-up (often called wet stacking). Run it on a real or test load where you can — see our generator load test guide.

Can the operator do the maintenance or do we need an engineer?

Daily and weekly checks are operator tasks. Scheduled services, load tests, protection tests and the annual inspection should be done by a trained engineer, and are what a generator AMC covers.

Do you service all makes of generator?

Yes. OVN services every major make of diesel generator across Delhi NCR, on call or under an annual maintenance contract.

Rather we did the checklist?

Share your genset list and run hours — we'll scope an AMC for the whole fleet.